Sensor status (cont’d) – System Sensor FAAST Modbus User Manual
Page 12

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1
12
Sensor Status (Cont’d)
Address
Size
(16-bit
words)
Parameter Name
Type
Description
52
½
Ch 3 Air Temperature
S8
Real-time sampled air temperature in Channel 3
(multichannel device only)
53
½
Ch 3 Air Velocity Change
S8
Percentage change from baseline air velocity in Channel 3
(multichannel device only)
54-55
2
Ch 3 Air Velocity Baseline
F32
Average velocity during baselining in Channel 3
(multichannel device only)
56-57
2
Ch 3 Air Velocity Daily Min
F32
Daily minimum air velocity realized on Channel 3
(multichannel device only)
58-59
2
Ch 3 Air Velocity Daily Max
F32
Daily maximum air velocity realized on Channel 3
(multichannel device only)
60
½
Ch 4 Air Temperature
S8
Real-time sampled air temperature in Channel 4
(multichannel device only)
61
½
Ch 4 Air Velocity Change
S8
Percentage change from baseline air velocity in Channel 4
(multichannel device only)
62-63
2
Ch 4 Air Velocity Baseline
F32
Average velocity during baselining in Channel 4
(multichannel device only)
64-65
2
Ch 4 Air Velocity Daily Min
F32
Daily minimum air velocity realized on Channel 4
(multichannel device only)
66-67
2
Ch 4 Air Velocity Daily Max
F32
Daily maximum air velocity realized on Channel 4
(multichannel device only)
68
½
Smoke Particulate Display
U8
Front panel particulate level (0-10)
69-70
2
Smoke Current Obs
F32
Current Obscuration Level the Smoke Sensor is Detecting
71-72
2
Smoke Daily Max Obs
F32
Maximum Obscuration Level the Smoke Sensor Detected
since 12am
73-74
2
Smoke Daily Min Obs
F32
Minimum Obscuration Level the Smoke Sensor Detected
since 12am
75-76
2
Alert Threshold
F32
Current Active Alert Threshold ( %/ft if US Standard or %/m
if metric)
77-78
2
Action1 Threshold
F32
Current Active Action1 Threshold ( %/ft if US Standard or
%/m if metric)
79-80
2
Action2 Threshold
F32
Current Active Action2 Threshold ( %/ft if US Standard or
%/m if metric)
81-82
2
Fire1 Threshold
F32
Current Active Fire1 Threshold ( %/ft if US Standard or %/m
if metric)
83-84
2
Fire2 Threshold
F32
Current Active Fire2 Threshold ( %/ft if US Standard or %/m
if metric)
85
1
Sensor Status
U16
Bit 0 – Admin Unlock
1 = Unlocked, 0 = Locked
Bit 1 –Baselining
1 = set (configured from sensor action inputs)
Table 4.
Sensor Status Modbus Holding Registers
∆
Information - Registers 35 can be configured by using Function code 6(single write) or Function 16 (multiple write).
∆
Warning!! Device threshold configuration variables should be set by the user to values scaled based on the Units configuration
setting. The detector will interpret the value differently for different Units settings. E.g. The device will interpret a 0.01 threshold
setting as 0.01 %/ft when Units setting is US Standard. The device will interpret a 0.01 threshold setting as 0.01 %/m when Units
setting is Metric.