A.2. device configuration variables – System Sensor FAAST Modbus User Manual
Page 19

User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1
19
Rev A0
A.2. Device Configuration Variables
Name
Description
Range
Default Value
Acclimate Mode Enable
Set to activate acclimate mode operation
Enable / Disable
Disabled
Alert Alarm Latch
Set to latch Alert alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching
Latching
Action1 Alarm Latch
Set to latch Action1 alarm. Requires a RESET to
clear alarm. This setting is only valid for conventional
product.
Latching/Non-Latching
Latching
Action2 Alarm Latch
Set to latch Action2 alarm. Requires a RESET to
clear alarm. This setting is only valid for conventional
product.
Latching/Non-Latching
Latching
Fire1 Alarm Latch
Set to latch Fire1 alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching
Latching
Fire2 Alarm Latch
Set to latch Fire2 alarm. Requires a RESET to clear
alarm. This setting is only valid for conventional
product.
Latching/Non-Latching
Latching
Alert Delay
Programmable delay before activating Alert Alarm.
This setting is only valid for conventional product.
0 - 60 seconds
0
Action1 Delay
Programmable delay before activating Action1
Alarm. This setting is only valid for conventional
product.
0 - 60 seconds
0
Action2 Delay
Programmable delay before activating Action2
Alarm. This setting is only valid for conventional
product.
0 - 60 seconds
0
Fire1 Delay
Programmable delay before activating Fire1 Alarm.
This setting is only valid for conventional product.
0 - 60 seconds
0
Fire2 Delay
Programmable delay before activating Fire2 Alarm.
This setting is only valid for conventional product.
0 - 60 seconds
0
PassCodeButtonLockout
Allows lockout feature of buttons.
0000 - 9999
1111
TEST Lockout
Setting for locking and unlocking of TEST button.
This setting is only valid for conventional product.
Locked / Unlocked For the lock
function to work the passcode
must be any value other than
0000
Locked
RESET Lockout
Setting for locking and unlocking of RESET button.
This setting is only valid for conventional product.
Locked
DISABLE Lockout
Setting for locking and unlocking of DISABLE button.
This setting is only valid for conventional product.
Locked
IP Address
IP address of the device
192.168.1.10
Subnet Mask
255.255.255.0
Gateway
192.168.1.1
Address
Device local address range
CLIP enabled product
Flashscan enabled product
Eclipse enabled product
0-255
1-99
1-159
1-255
1
Time
Real time clock time in hours/minutes/seconds
Midnight
Date
Real time clock date
Current date
Year
Real time clock year
Current year
Log Setting
Configures the method of Event logging for either
FIFO (first in first out) or LIFO (last in first out) setting
FIFO / LIFO
FIFO
Password User
Password for Web Access User entry
Monitor
Table 10.
Device Configuration Variable Ranges.