SPEED #3 value . See Parameter 3 - SPEED #3 in Section 18 .0 - DESCRIPTION OF
PARAMETERS,
I LIMIT
CURRENT LIMIT - The relay energizes when the drive is operating in current limit.
Once the current limit relay is energized, it remains energized for a minimum of
500ms, regardless of whether the drive is still in current limit . At the end of the 500ms
interval, the relay will de-energize if the drive is no longer in current limit. See
Parameter 16 - CURRENT in Section 18 .0 - DESCRIPTION OF PARAMETERS .
AUT/MAN
AUTO/MANUAL MODE - The relay energizes when the drive is in the
AUTOMATIC mode, and de-energizes in the MANUAL mode. Refer to Section
14 .2 .5 - SPEED REFERENCE SELECTION .
FLWR PR
FOLLOWER PRESENT - The relay energizes when the analog input reference signal
at TB-5B is greater than 2 mA, and de-energizes if the signal falls below 2 mA.
REVERSE
The relay energizes when Reverse direction is selected, and de-energizes when Forward
direction is selected .
MIN/MAX
ALARM
The relay energizes when the feedback signal (in PID mode) or the speed reference
signal (in open-loop speed mode) is within the limits set by MIN ALARM and MAX
ALARM (Parameters 81 and 82), and de-energizes when the signal falls below the MIN
ALARM setting or exceeds the MAX ALARM setting.
INV
MIN/MAX A
INVERSE MIN/MAX ALARM - The relay de-energizes when the feedback signal
(in PID mode) or the speed reference signal (in open-loop speed mode) is within the
limits set by MIN ALARM and MAX ALARM (Parameters 81 and 82), and energizes
when the signal falls below the MIN ALARM setting or exceeds the MAX ALARM
setting .
MIN ALARM
The relay de-energizes when the feedback signal (in PID mode) or the speed refer-
ence signal (in open-loop speed mode) equals or exceeds the MIN ALARM setting
(Parameter 81), and energizes when the signal falls below the MIN ALARM setting.
INV MIN
ALARM
INVERSE MIN ALARM - The relay energizes when the feedback signal (in PID
mode) or the speed reference signal (in openloop speed mode) equals or exceeds the
MIN ALARM setting (Parameter 81), and de-energizes when the signal falls below the
MIN ALARM setting .
MAX ALARM
The relay de-energizes when the feedback signal (in PID mode) or the speed reference
signal (in open-loop speed mode) is less than or equal to the MAX ALARM setting
(Parameter 82), and energizes when the signal exceeds the MAX ALARM setting.
INV MAX
ALARM
INVERSE MAX ALARM - The relay energizes when the feedback signal (in PID
mode) or the speed reference signal (in open-loop speed mode) is less than or equal to
the MAX ALARM setting (Parameter 82), and de-energizes when the signal exceeds the
MAX ALARM setting .
SLEEP
The relay energizes when the drive is in SLEEP MODE. See Parameters 36 - 38.
70