LEESON Micro Series Compact Inverters User Manual
Page 64

27 ROTATION
(ROTATION DIRECTION)
If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a
STOP switch! This is true in LOCAL and REMOTE mode. Incorrect use of TB-1 may result
in damage to equipment and/or injury to personnel! Refer to Parameter 49 - TB13C for more
information .
This parameter is used to limit the motor rotation direction to forward or reverse, or to allow rotation in
both directions . The parameter can be set to one of the following:
FORWARD
Rotation is allowed in the forward direction only . This selection disables the
FWD/REV button the keypad and TB-13C (REVERSE).
REVERSE
Rotation is allowed in the reverse direction only . This selection disables the FWD/REV
button on the keypad and TB-12A (FORWARD). TB-13C must be programmed for
either RUN REV or STRT REV for this function to operate in the REMOTE mode .
FWD&REV
Rotation is allowed in both directions . The FWD/REV button is enabled . Rotation can
be changed form the keypad (LOCAL mode), or the terminal strip (REMOTE mode).
In the REMOTE mode, TB-13C must be programmed for either RUN REV or STRT
REV for this function to operate .
FWD@LOC
In LOCAL mode, rotation is allowed in the forward direction only . In REMOTE
mode, rotation is allowed in both directions .
NOTE:
If the rotation is changed while the drive is running, the drive will decelerate to 0 Hz, and then
accelerate back up to the speed set point in the opposite direction.
28 AUTO/MAN
(AUTO/MANUAL SPEED CONTROL)
This parameter is used to select the method of speed control when the drive is in the LOCAL mode . The
choices are explained below:
MANUAL
The drive will accept a speed reference from the keypad (UP and DOWN ARROW
keys) or a speed potentiometer (wired to TB-2, 5A, and 6). Parameter 29 - MANUAL
below selects either keypad or speed potentiometer. The AUTO/MAN button on the
keypad is disabled.
AUTO
The drive will accept a 0-10 VDC input signal on TB-5A and TB-2, a 4-20 mA input
signal on TB-5B and TB-2, or one of the four PRESET SPEEDS . The programming
of TB-13A, TB-13B and TB-13C determines which AUTO reference is selected . The
AUTO/MAN button on the keypad is disabled.
BOTH
The AUTO/MAN key on the keypad is enabled and can be used to toggle between
MANUAL and AUTO control ONLY if if the drive is in LOCAL mode .
NOTE:
If the drive is in the AUTO mode, and a speed reference is not selected using TB-13A, TB-13B,
or TB-13C, the speed reference source will default to the setting of Parameter 29 - MANUAL (KEYPAD
or 0-10 VDC).
62
WARNING