LEESON Micro Series Quick Reference Guide User Manual
Leeson, Micro series quick reference guide, Variable speed ac motor drives
![background image](/manuals/351339/1/background.png)
LEESON
Variable Speed AC Motor Drives
RUN
60.00 HZ
PROG
RUN
AUTO
MAN
START
ENTER
FWD
REV
STOP
Micro Series
Quick Reference Guide
NOTE: Before installing and operating the MICRO SERIES
drive, please read and become familiar with the MICRO SERIES
Installation and Operation Manual.
Adjustable Speed AC Motor Control
2
OUTPUT
ACCEL
In the example above, the second fault is being viewed, which is
an OUTPUT fault that occurred while the drive was accelerating.
FAULT
NUMBER
FAULT
MESSAGE
DRIVE
STATUS
MICRO SERIES FAULT HISTORY
Parameter 70 — FAULT HISTORY stores the last eight faults that
tripped the drive. The FAULT HISTORY indicates the number of
the fault (number 1 is the most recent fault), the fault message,
and the status of the drive at the time of the fault. An example is
shown below:
FAULT
DESCRIPTION
OUTPUT
Output Transistor fault. Output current exceeded 200%.
May be ground fault or short circuit.
LO VOLTS
Low DC Bus Voltage fault. DC bus voltage dropped below 60%
May be low line voltage.
HI VOLTS
High DC Bus Voltage fault. DC Bus voltage exceeded 120%.
May be overhauling load .
HI TEMP
High Temperature fault. Heatsink or ambient temperature
too high.
OVERLOAD
Current Overload fault. Output current exceeded 100% for
too long. VFD may be undersized.
PWR TRAN
Power Transient fault.
PWR SAG
Power Sag fault: New control board installed. Perform
factory reset using Parameter 65.
LANGUAGE
Language EEPROM fault.
EXTERNAL
External fault: TB-130 activated (Parameter 50).
DB ERROR
Dynamic Brake fault. DB Resistors overloaded.
CONTROL
Control Board fault. New solfware installed. Perform factory
reset using Parameter 65.
INTERNAL
Internal fault
INTERN (#)
Internal fault.
MC3000 FAULT MESSAGES
PARAMETER
FACTORY
PARAMETER
FACTORY
NO.
NAME
DEFAULT
NO.
NAME
DAFAULT
0
LINE VOLTS
AUTO
1
SPEED #1
20.00 Hz
2
SPEED #2
20.00 Hz
3
SPEED #3
20.00 Hz
4
SPEED #4
20.00 Hz
5
SKIP #1
.00 Hz
6
SKIP #2
.00 Hz
7
BAND WID
1.00 Hz
8
ACCEL
30.0 SEC
9
DECEL
30.0 SEC
10
MIN FRQ
.50 Hz
11
MAX FRQ
60.00 Hz
12
DC BRAKE
.0 VDC
13
DC TIME
.0 SEC
14
DYN BRAKE
OFF
16
CURRENT
180%
17
MOTOR OL
100%
18
BASE
60.00 Hz
19
FX BOOST
(NOTE 1)
20
AC BOOST
.0%
21
SLIP COMP
.0%
22
TORQUE
CONSTANT
23
CARRIER
2.5 kHz
25
START
NORMAL
26
STOP
COAST
27
ROTATION
FORWARD
28
AUTO/MAN
BOTH
29
MANUAL
KEYPAD
30
CONTROL
LOCAL
31
UNITS
HERTZ
32
HZ MULT
1
33
UNITS DP
XXXX
34
LOAD MLT
100%
35
CONTRAST
HIGH
39
TB5 MIN
.00 Hz
40
TB5 MAX
60.00 Hz
42
TB10A OUT
NONE
43
@TB10A
60.00 Hz
44
TB10B OUT
NONE
45
@TB10B
125%
47
TB13A
NONE
48
TB13B
NONE
49
TB13C
NONE
50
TB13D
FAULT
52
TB14 OUT
NONE
53
TB15 OUT
NONE
54
RELAY
NONE
58
ADDRESS
30
61
PASSWORD
0019
63
SOFTWARE
(NOTE 2)
64
MONITOR
ON
65
PROGRAM
RESET 60
66
HISTORY
MAINTAIN
70
FAULT HIST.
(NOTE 2)
NOTE 1: REFER TO THE MICRO SERIES MANUAL.
NOTE 2: THESE PARAMETERS ARE VIEW-ONLY.
MICRO SERIES PARAMETERS
Micro Series
Intelligent Drive
Digital
LEESON SPEEDMASTER
BULLETIN #2452 3/98