The Enable function is established by

wiring a switch or contact in series with

the orange Main Speed Potentiometer

lead which connects to Terminal “P2”.

When the Enable Switch is closed, the

motor will accelerate to the Main

Speed Potentiometer setting. When

the Enable Switch is opened, the

motor will decelerate to stop.

WARNING! If the Enable

Switch is to be mounted

remotely, it is highly recommended

that the SIAC Signal Isolator

(Part No. 9600) be installed.

5.9

Run/Fault Relay Connection – The Run/Fault

Relay Output Contacts are located at TB2 and

can be used to turn on or off equipment or to

signal a warning if the drive is put into the Stop

Mode or a fault has occurred. See Figure 15.

The Run/Fault Relay Contact status for various

drive operating conditions is shown in Table 6.

FIGURE 14 – ENABLE CIRCUIT CONNECTION

Main Speed

Potentiometer

Enable Switch or Relay

Orange (Wiper)
Violet (High)

White (Low)

(Close to Run)

P1

P2

P3

FIGURE 15 – RUN/FAULT RELAY OUTPUT

CONTACTS CONNECTION

Output Contacts

Run/Fault Relay

Normally Closed

Relay Common

Normally Open

NC

NO

TB2

COM

6

SETTING SELECTABLE JUMPERS

The drive has customer selectable

jumpers which must be set before

the drive can be used. For the

location of jumpers, see Figure 2,

on page 9.

Note: Disconnect the AC line

before changing position of

jumpers.

6.1

LINE INPUT VOLTAGE

SELECTION (J1 (MODELS

KBAC-24D, 27D ONLY)) –

Jumper J1 is factory installed

on Terminal “230V” for 208/230 Volt AC line input. For 115 Volt AC line input, the jumper must be

removed and installed on Terminal “115V”. See Figure 16.

Drive

Operating

Condition

Description

Run Relay Operation

(Jumper J8 Installed in “R” Position)

(Factory Setting)

Fault Relay Operation

(Jumper J8 Installed in “F” Position)

Normally

Open Contact

Normally

Closed Contact

Normally

Open Contact

Normally

Closed Contact

Power Off

Main Power Disconnected

Open

Closed

Open

Closed

Run Mode*

Normal Drive Operation

Closed

Open

Closed

Open

Stop Mode*

Selected by Operator

Open

Closed

Closed

Open

Fault**

Drive Tripped

Open

Closed

Open

Closed

TABLE 6 – DRIVE OPERATING CONDITION AND RUN/FAULT RELAY CONTACT STATUS

*Run Mode or Stop Mode is selected using the Start/Stop Switch. **Overload, I

2

t, Short Circuit, Undervoltage, Overvoltage.

FIGURE 16 – MODELS KBAC-24D*, 27D AC LINE INPUT VOLTAGE SELECTION

208/230 Volt AC Line Input

(Factory Setting)

(J1 Installed on Terminal “230V”)

115 Volt AC Line Input

(J1 Installed on Terminal “115V”)

115V

J1

230V

J1

115V

230V

*Layout of Model KBAC-24D varies slightly.