beautypg.com

Ransburg, Troubleshooting guide, Cont.) – Ransburg Evolver MicroPak Controller A10406 User Manual

Page 27: Evolver micropak controller - maintenance

background image

General Problem

Possible Cause

Solution

TROUBLESHOOTING GUIDE

(Cont.)

Improper interlock connection.

High voltage ready condition not

activated.

High Voltage On input not activated.

Defective MicroPak Control Unit.

Ensure interlock connection is connected

to ground through a jumper or voltage free

contact as detailed in the “Installation” sec-

tion of this manual.

Activate the high voltage ready input or set

dipswitch 3-3 to the OFF position.

Supply 24VDC to the High Voltage On input

or if in manual mode, move the High Voltage

Enable switch to the ON position.

If none of the suggestions above resolves the

issue, replace the LECU5004-31 MicroPak

Control Unit.

Parts are too close to the spray gun.

Overload setpoint set too sensitive.

Defective spray gun or cable.

Defective MicroPak Control Unit.

Ensure sufficient distance between spray

gun and parts.

Increase the μA setpoint using the μA Adjust

Knob, process board potentiometer R21, or

the 0-10VDC over-current setpoint input.

Perform a Cable Continuity Test. If proper

readings are not obtained, check cable or

spray gun for cause (see current “Spray

Gun” service manual).

If none of the suggestions above resolves the

issue, replace the LECU5004-31 MicroPak

Control Unit.

Ready input is active and dipswitch

SW3-3 is off.

Wiring to/from component loose or

broken.

Defective component.

Disable ready input or turn dipswitch

SW3-3 off.

Repair loose or broken wire.

Replace component.

No kV Output at

Spray Gun and HV

ON Indicator (red

LED) is not Lit

Power Supply

Overloads

Excessively

High Voltage on all

the time.
Component not

working, but kV

Output OK.

Evolver MicroPak Controller - Maintenance

Ransburg

24

LN-9622-00.5