INTERLOCKS AND I/O

Interlock and I/O connections are made to con-

nector P3 on the rear of the controller. P3 consists

of three, 8-position terminal blocks A, B, and C

(see Figure 3). To wire to these terminal blocks,

perform the following (see Figure 4):

1. Loosen the 2 screws of P3’s connector housing

and remove P3 from the controller.

2. Loosen the 4 screws holding the terminal block

assembly to the inside of the connector housing

and remove the terminal block assembly from

the housing.

3. Feed the I/O / Interlock cable(s) through the

cable grommet attached to the connector housing

and pull out the other side. It may be necessary

to remove the cable grommet to fit the cable(s)

through. If so, slide the grommet connections onto

the cable(s) in the order shown in Figure 4 before

pulling the cable through the connector housing.

†

For maximum noise immunity, all wir-

ing should be run in cables having a foil

shield with an overall braided shield. The

foil shield provides 100% shielding, while

the braid provides a means of making

proper 360° shield terminations at the ca-

ble ends.

NOTE

If multiple I/O / Interlock cables are used,

connect the exposed 1.5” cable braids

together using copper tape.

NOTE

4. Strip the jacket off the cable(s) 3” from the

end and remove the braid 1.5” from the end (see

Figure 5).

5. Strip the individual cable wires, install appro-

priate wire ferrules, and connect to the terminal

blocks according to Table 1.

6. Rotate the connector housing to achieve de-

sired routing of the cable bundle (right or left),

then reinstall the terminal block assembly into the

connector housing.

7. Tighten the connector grommet ensuring the

grommet spring makes 360° contact with the

exposed cable braid/copper tape for maximum

noise immunity.

For maximum noise immunity, the shields of the I/O

and interlock cables should also be connected to

earth ground at the end opposite to the MicroPak

controller connections.

If it is necessary or desired to run the interlock and

I/O cable(s) through conduit, an adapter can be

readily purchased that converts the PG21 male

threads of the P3 connector housing to 3/4” NPT

male threads. This adapter is available through

McMaster-Carr as their Part Number 7842K7.