DIP SWITCH SUMMARY

(See Figure 6A & 6B)

MicroPak Process Board

Dipswitch SW3-1

In remote mode, determines whether over-current

setpoint control is provided by the remote Over-

current Setpoint analog input or from R21 of the

MicroPak process board. If dipswitch SW3-1 is ON

control is from the remote analog input. If dipswitch

SW3-1 is OFF control is from potentiometer R21.

MicroPak Process Board

Dipswitch SW3-3

Determines whether high voltage is enabled

when ready mode is active. If dipswitch SW3-3 is

ON, high voltage is NOT enabled in ready mode.

Therefore, separate ready and high voltage enable

signals are required to enable high voltage. This

is the typical setting for remote mode. If dipswitch

SW3-3 is OFF, high voltage IS enabled when

ready mode becomes active. This is the typical

setting for local (manual) mode, so that pushing

the High Voltage Enable Switch to the ON position

will enable high voltage output without requiring

a ready signal.

Inputs:

P3 Terminal

kV Setpoint (0-10VDC)

C4

Overcurrent Setpoint (0-10VDC)

C3

High Voltage Reset (24VDC)

C2

High Voltage On (24VDC)

C1

Ready

A1

Outputs:
Overload (24VDC)

B4

HV Ready (24VDC)

B3

HV On (24VDC)

B2

Interlock:
Interlock Line A

A3

Other:
Ground

B1

Ground

A2

Table 1 - Electrical I/O

Discrete I/O Board Dipswitch

SW2-1

This dipswitch is set according to the cascade in

use with the MicroPak Control Unit. It is factory

set to the ON position for use with the HP404 FM

cascade in the Evolver applicator.

W A R N I N G

!

†

Dipswitch SW3-3 should never be set

to OFF while the remote Ready input is ac-

tive or high voltage will be on all of the time

(whenever AC power is on).

MicroPak 1

Inputs:

P3 Terminal

kV Setpoint (0-10VDC)

C8

Overcurrent Setpoint (0-10VDC)

C7

High Voltage Reset (24VDC)

C6

High Voltage On (24VDC)

C5

Ready

A5

Outputs:
Overload (24VDC)

B8

HV Ready (24VDC)

B7

HV On (24VDC)

B6

Interlock:
Interlock Line A

A7

Other:
Ground

B5

Ground

A6

MicroPak 2

Evolver MicroPak Controller - Installation

Ransburg

16

LN-9622-00.5