beautypg.com

Ransburg, Other terminals, Evolver micropak controller - installation – Ransburg Evolver MicroPak Controller A10406 User Manual

Page 18

background image

Ready

Remote input used to put the MicroPak Control

Unit in ready mode. This input is made active by

a momentary ground connection. Once active, it

can only be deactivated by activating the remote

High Voltage Reset input or by momentarily moving

the High Voltage Enable switch (see Figure 8) to

the OFF position. This input must be made active

(grounded) before high voltage can be enabled

using the remote High Voltage On input. This can

be done externally or by hardwiring this input to the

P3-A2 ground connection for MicroPak #1 or the

P3-A6 ground connection for MicroPak #2. When

hardwired to ground, the MicroPak will be in HV

ready mode whenever there are no faults present

and the High Voltage Reset Input is not active.

W A R N I N G

!

†

When using the remote Ready input en-

sure dipswitch SW3-3 is in the ON position, or

high voltage to the applicator will be enabled

whenever the Ready input is made active.

†

When in local mode and dipswitch

SW3-3 is set to the OFF position HV Ready

and HV On will occur at the same time.

NOTE

Output Terminals

Each 24 VDC output is supplied through a relay

contact capable of handling up to 1 amp of cur-

rent. However, if one or more outputs are active

at the same time, the total output current should

not exceed 2 amps.

Overload (24VDC)

Remote output signal that puts out 24VDC when

an over-current fault occurs.

HV Ready (24VDC)

Remote output signal that puts out 24VDC when

the MicroPak is in high voltage ready mode. High

voltage ready mode occurs when there are no fault

conditions present, the high voltage has not yet

been enabled and either the High Voltage Enable

Switch is moved to the ON position or the remote

Ready input is activated.

HV On (24VDC)

Remote output signal that puts out 24VDC when

high voltage is enabled.

Interlock Terminal

Terminal that allows interlocking of high voltage

with safety components. In order to obtain high

voltage, the interlock terminal for the respective

MicroPak control unit must be connected to ground

by a jumper or voltage free contact. If the high

voltage is enabled without the interlock terminal

being connected to ground, high voltage output

will not occur. This terminal is a convenient place

to interlock the controller with the exhaust fan and

conveyor as required by NFPA-33. If the interlock

connection is momentarily lost, the connection

must be restored and the high voltage re-enabled

before the high voltage output will turn back on.

Other Terminals

Ground

Terminals supplied for ground connections of

various inputs and outputs.

Evolver MicroPak Controller - Installation

Ransburg

15

LN-9622-00.5