5. Supply a momentary ground connection to the

Ready input shown in Table 1. The yellow High

Voltage Ready Indicator should turn on.

6. Supply a 24VDC signal to the High Voltage On

input shown in Table 1. The red High Voltage On

Indicator should turn on.

7. Adjust the 0-10VDC kV setpoint input to obtain

the desired value on the kV Meter. Ensure the

over-current setpoint is set above the maximum

expected current, or an overload fault will occur.

Figure 8: Operating Controls

The over-current setpoint can be adjusted by

changing the setpoint of R21 if dipswitch SW3-1

is OFF, or by changing the value of the 0-10VDC

over-current setpoint input (see Table 1) if dipswitch

SW3-1 is ON.

8. To turn high voltage off, remove the 24VDC

signal from the high voltage on input.

9. When finished spraying, turn the AC Power ON/

OFF Switch (see Figure 2) to the OFF position to

prolong the life of the internal fan.

Evolver MicroPak Controller - Operation

Ransburg

21

LN-9622-00.5