E-Mon E50-6003200J*-N-KIT User Manual
Page 45
![background image](/manuals/345946/45/background.png)
GREEN CLASS NET METER
45
62-0416-01
BACnet Object Descriptors (continued):
27 Analog Input Current phase A
Amps
Present Value R
28 Analog Input Current phase B
Amps
Present Value R
29 Analog Input Current phase C
Amps
Present Value R
30 Analog Input Voltage line-neutral phase A-N Volts-N Present Value R
31 Analog Input Voltage line-neutral phase B-N Volts-N Present Value R
32 Analog Input Voltage line-neutral phase C-N Volts-N Present Value R
33 Analog Input Voltage line-line phase A-B
Volts-L Present Value R
34 Analog Input Voltage line-line phase B-C
Volts-L Present Value R
35 Analog Input Voltage line-line phase C-A
Volts-L Present Value R
36 Analog Input Phase angle phase A
Degree Present Value R
37 Analog Input Phase angle phase B
Degree Present Value R
38 Analog Input Phase angle phase C
Degree Present Value R
39 Analog Input Reserve A
40 Analog Input Reserve B
41 Analog Input Reserve C
42* Analog Input External Input 1
Pulse
Present Value R
43* Analog Input External Input 2
Pulse
Present Value R
*External inputs are standard on Class 5000 meters and optional on Class 3400 meters (Part of
Expanded Feature Package).
Lonworks SNVT Types Point Map:
Network Variable
Name
SNVT Type
Description
Units
CL5000
nvoKWh_Del
SNVT_count_inc_f Energy delivered
kWh
R
nvoKWh_Rec
SNVT_count_inc_f Energy received
kWh
R
nvoKVarh_Del
SNVT_count_inc_f Reactive energy
delivered
kVARh R
- E50-6001600J*-N-KIT E50-600800-J*-N-KIT E50-600400-J*-N-KIT E50-600200-J*-N-KIT E50-600100-J*-N-KIT E50-4803200J*-N-KIT E50-4801600J*-N-KIT E50-480800-J*-N-KIT E50-480400-J*-N-KIT E50-480200-J*-N-KIT E50-480100-J*-N-KIT E50-4003200J*-N-KIT E50-4001600J*-N-KIT E50-400800-J*-N-KIT E50-400400-J*-N-KIT E50-400200-J*-N-KIT E50-400100-J*-N-KIT E50-2083200J*-N-KIT E50-2081600J*-N-KIT E50-208800-J*-N-KIT E50-208400-J*-N-KIT E50-208200-J*-N-KIT E50-208100-J*-N-KIT