6.7 RS-485 Wiring (continued)
After performing these steps, all of the meters will be connected in a daisy chain
configuration. This network of meters can then be connected to the RS-485 network
and communication can be established.
Internal Modem
An optional internal modem inside one meter will communicate with the others via the
RS-485 network. Simply connect one of the two telephone jacks on the modem to the
telephone line to complete the installation.
Local Computer
A local computer installed in the building can communicate with the RS-485 network.
The computer must be connected to an RS-232 key. The RS-232 key is then
connected to an available RS-485 jack in the meter using an RJ-11 cable.
NOTE: Don’t confuse the modem’s telephone jacks with the RS-485 jacks!!!
NOTE: When using one meter with an external modem, only the telephone line is
connected. RS-485 is not needed.
- E50-6001600J*-N-KIT E50-600800-J*-N-KIT E50-600400-J*-N-KIT E50-600200-J*-N-KIT E50-600100-J*-N-KIT E50-4803200J*-N-KIT E50-4801600J*-N-KIT E50-480800-J*-N-KIT E50-480400-J*-N-KIT E50-480200-J*-N-KIT E50-480100-J*-N-KIT E50-4003200J*-N-KIT E50-4001600J*-N-KIT E50-400800-J*-N-KIT E50-400400-J*-N-KIT E50-400200-J*-N-KIT E50-400100-J*-N-KIT E50-2083200J*-N-KIT E50-2081600J*-N-KIT E50-208800-J*-N-KIT E50-208400-J*-N-KIT E50-208200-J*-N-KIT E50-208100-J*-N-KIT