6.7 RS-485 Wiring
RS-485 communication allows a computer or modem to communicate with one or
more Green Class Net meters. You can connect as many as 52 meters along a 4000-
foot RS-485 cable run.
There are four communication protocols available through the Green Class Net RS-
485 connection. They are EZ7, Modbus RTU, BACnet MS/TP, and Lonworks FT-10.
The protocol is chosen when ordering the Green Class Net meter. A second protocol is
available through the Ethernet port. The Ethernet protocol is also chosen when the
meter is ordered. See ordering information for the available choices.
Daisy-Chain Method
This is the simplest method for connecting meters together.
Fig. 9. Daisy-Chain Configuration.
1. Connect the +(high) terminal of PORT 1 of each meter together so that the + ter-
minals on all meters are linked, + to + to +...
2. Connect the -(low) terminal of PORT 1 of each meter together so that the - termi-
nals on all meters are linked, - to - to -...
3. Connect the GND terminals of PORT 1 of each meter so that the GND terminals
on all meters are linked, GND to GND to GND.
Fig. 10. RS-485 Terminal.
M32776
RS-485
TERMINAL
M33274
- E50-6001600J*-N-KIT E50-600800-J*-N-KIT E50-600400-J*-N-KIT E50-600200-J*-N-KIT E50-600100-J*-N-KIT E50-4803200J*-N-KIT E50-4801600J*-N-KIT E50-480800-J*-N-KIT E50-480400-J*-N-KIT E50-480200-J*-N-KIT E50-480100-J*-N-KIT E50-4003200J*-N-KIT E50-4001600J*-N-KIT E50-400800-J*-N-KIT E50-400400-J*-N-KIT E50-400200-J*-N-KIT E50-400100-J*-N-KIT E50-2083200J*-N-KIT E50-2081600J*-N-KIT E50-208800-J*-N-KIT E50-208400-J*-N-KIT E50-208200-J*-N-KIT E50-208100-J*-N-KIT