GREEN CLASS NET METER

43

62-0416-01

Modbus Float Registers (continued):

41047

2

Power factor, phase A

% PF

R

41049

2

Power factor, phase B

% PF

R

41051

2

Power factor, phase C

% PF

R

41053

2

Current, phase A

Amps

R

41055

2

Current, phase B

Amps

R

41057

2

Current, phase C

Amps

R

41059

2

Voltage, line to neutral, phase A-N

Volts-N

R

41061

2

Voltage, line to neutral, phase B-N

Volts-N

R

41063

2

Voltage, line to neutral, phase C-N

Volts-N

R

41065

2

Voltage, line to line, phase A-B

Volts-L

R

41067

2

Voltage, line to line, phase B-C

Volts-L

R

41069

2

Voltage, line to line, phase C-A

Volts-L

R

41071

2

Phase angle, phase A

Degree

R

41073

2

Phase angle, phase B

Degree

R

41075

2

Phase angle, phase C

Degree

R

41077

2

Reserved

41079

2

Reserved

41081

2

Reserved

41083*** 2

External Input 1

Pulse

R/W

41085*** 2

External Input 2

Pulse

R/W

**

To clear single meter kWh/kVARh, set multiple points at 41001 for 8 points with data set to 0000

0000 0000 0000 0000 0000 0000 0000. Jumper J6 m

***

External inputs are standard on Class 5000 meters and optional on Class 3400 meters (Part of

Expanded Feature Package).To clear Auxiliary Inputs, set multiple points at 41083 or 41085 for 2
points with data set to 0000 0000. Jumper J6 must be closed.

BACnet Object Descriptors:

ID

BACnet

Object

Description

Units

BACnet

Property

CL

5000

1

Analog Input Energy delivered

kWh

Present Value R

2

Analog Input Energy received

kWh

Present Value R

3

Analog Input Reactive energy delivered

kVARh Present Value R

4

Analog Input Reactive energy received

kVARh Present Value R