6.4.2 Current Sensor Wiring (continued)
If the meter displays an error message (see below), remove the wires from terminals 5
and 6 and install them on terminals 7 and 8 (Phase B). if an error message occurs with
the sensor attached to terminals 7 and 8, try again on terminals 9 and 10 (Phase C).
The “CT Error: * “message will disappear when the current sensor is connected to the
correct terminals (phase).
Error Messages: CT ERROR: A
CT ERROR: A B
CT ERROR: A C
Refer to the section on Current Sensor Diagnostics for assistance in troubleshooting
these errors.
6.4.3 Main Power
After the meter circuit wiring has been examined for correctness, power may be
applied to the circuit board. There are three LEDs located in the upper right corner of
the Meter Board labeled BEAT, STATUS and LOAD. The BEAT and STATUS LEDs will
blink once per second when the meter is operating normally, twice per second if there
is a problem. If the monitored circuit is under load the LOAD LED will actively blink. A
heavy load will cause the LED to blink faster than a light load. Very light loads will
result in an extended blink time.
- E50-6001600J*-N-KIT E50-600800-J*-N-KIT E50-600400-J*-N-KIT E50-600200-J*-N-KIT E50-600100-J*-N-KIT E50-4803200J*-N-KIT E50-4801600J*-N-KIT E50-480800-J*-N-KIT E50-480400-J*-N-KIT E50-480200-J*-N-KIT E50-480100-J*-N-KIT E50-4003200J*-N-KIT E50-4001600J*-N-KIT E50-400800-J*-N-KIT E50-400400-J*-N-KIT E50-400200-J*-N-KIT E50-400100-J*-N-KIT E50-2083200J*-N-KIT E50-2081600J*-N-KIT E50-208800-J*-N-KIT E50-208400-J*-N-KIT E50-208200-J*-N-KIT E50-208100-J*-N-KIT