beautypg.com

0 modbus point maps – E-Mon E50-6003200J*-N-KIT User Manual

Page 42

background image

GREEN CLASS NET METER

62-0416-01

42

12.0 MODBUS POINT MAPS

Modbus Integer Registers:

Address

Reg Description

Units

CL5000

40001*

2

Energy delivered

kWh Pulse

R/W

40003

2

Energy received

kWh Pulse

R/W

40005

2

Reactive energy delivered

kVARh Pulse

R/W

40007

2

Reactive energy received

kVARh Pulse

R/W

* To clear single meter kWh/kVARh, set multiple points at 40001 for 8 points with

data set to 0000 0000 0000 0000 0000 0000 0000 0000. Jumper J6 must be

closed.

Modbus Float Registers:

Address Reg Description

Units

CL5000

41001**

2

Energy delivered

kWh

R/W

41003**

2

Energy received

kWh

R/W

41005**

2

Reactive energy delivered

kVARh

R/W

41007**

2

Reactive energy received

kVARh

R/W

41009

2

Real power

kW

R

41011

2

Reactive power

kVARh

R

41013

2

Apparent power

kVARh

R

41015

2

Power factor

% PF

R

41017

2

Current total

Amps

R

41019

2

Current average

Amps

R

41021

2

Voltage line-neutral

Volts-N

R

41023

2

Voltage line-line

Volts-L

R

41025

2

Frequency

Hz

R

41027

2

Phase angle

Degree

R

41029

2

Real power, phase A

kW

R

41031

2

Real power, phase B

kW

R

41033

2

Real power, phase C

kW

R

41035

2

Reactive power, phase A

kVAR

R

41037

2

Reactive power, phase B

kVAR

R

41039

2

Reactive power, phase C

kVAR

R

41041

2

Apparent power, phase A

kVA

R

41043

2

Apparent power, phase B

kVA

R

41045

2

Apparent power, phase C

kVA

R