12.0 MODBUS POINT MAPS
Modbus Integer Registers:
Address
Reg Description
Units
CL5000
40001*
2
Energy delivered
kWh Pulse
R/W
40003
2
Energy received
kWh Pulse
R/W
40005
2
Reactive energy delivered
kVARh Pulse
R/W
40007
2
Reactive energy received
kVARh Pulse
R/W
* To clear single meter kWh/kVARh, set multiple points at 40001 for 8 points with
data set to 0000 0000 0000 0000 0000 0000 0000 0000. Jumper J6 must be
closed.
Modbus Float Registers:
Address Reg Description
Units
CL5000
41001**
2
Energy delivered
kWh
R/W
41003**
2
Energy received
kWh
R/W
41005**
2
Reactive energy delivered
kVARh
R/W
41007**
2
Reactive energy received
kVARh
R/W
41009
2
Real power
kW
R
41011
2
Reactive power
kVARh
R
41013
2
Apparent power
kVARh
R
41015
2
Power factor
% PF
R
41017
2
Current total
Amps
R
41019
2
Current average
Amps
R
41021
2
Voltage line-neutral
Volts-N
R
41023
2
Voltage line-line
Volts-L
R
41025
2
Frequency
Hz
R
41027
2
Phase angle
Degree
R
41029
2
Real power, phase A
kW
R
41031
2
Real power, phase B
kW
R
41033
2
Real power, phase C
kW
R
41035
2
Reactive power, phase A
kVAR
R
41037
2
Reactive power, phase B
kVAR
R
41039
2
Reactive power, phase C
kVAR
R
41041
2
Apparent power, phase A
kVA
R
41043
2
Apparent power, phase B
kVA
R
41045
2
Apparent power, phase C
kVA
R
- E50-6001600J*-N-KIT E50-600800-J*-N-KIT E50-600400-J*-N-KIT E50-600200-J*-N-KIT E50-600100-J*-N-KIT E50-4803200J*-N-KIT E50-4801600J*-N-KIT E50-480800-J*-N-KIT E50-480400-J*-N-KIT E50-480200-J*-N-KIT E50-480100-J*-N-KIT E50-4003200J*-N-KIT E50-4001600J*-N-KIT E50-400800-J*-N-KIT E50-400400-J*-N-KIT E50-400200-J*-N-KIT E50-400100-J*-N-KIT E50-2083200J*-N-KIT E50-2081600J*-N-KIT E50-208800-J*-N-KIT E50-208400-J*-N-KIT E50-208200-J*-N-KIT E50-208100-J*-N-KIT