Teledyne 7600 - Infrared gas analyzer - communication manual User Manual
Page 22

Teledyne Analytical Instruments
22
(2) Function explanations
Word data of continuous word number is written from write-in start address. Write-in word
data are transmitted from master station in the order of upper and lower bytes.
(3) Message transmission (example)
The following shows an example of writing the CH1 (1st component) alarm settings to No. 1
station.
CH1 range-1 high alarm setting = 1388
H
(= 5000
D
)
CH1 range-1 low alarm setting = 000A
H
(= 10
D
)
CH1 range-2 high alarm setting = 03E8
H
(= 1000
D
)
CH1 range-2 low alarm setting = 000A
H
(= 10
D
)
CH1 range-1 high alarm setting
Relative address: 0023
H
Data number: 04
H
Command message composition (byte)
Response message composition (byte)
Station No.
01
H
Station No.
01
H
Function code
10
H
Function code
10
H
Upper
00
H
Upper 00
H
Write-in word number
Lower
04
H
Write-in start No.
Lower 23
H
Upper 00
H
Write-in byte number
08
H
Write-in word number
Lower 04
H
Upper
13
H
Lower 30
H
First write-in word data
Lower
88
H
CRC data
Upper 00
H
Upper
00
H
Next write-in word data
Lower
0A
H
Upper
03
H
Next write-in word data
Lower
E8
H
Upper
00
H
Last write-in word data
Lower
0A
H
Lower
E2
H
CRC data
Upper
A6
H
Since the transmission data can not include a decimal point, data of 500.0 is transmitted as
"5000".
For transmission format of each data, refer to the Address map (Chapter 7).