Maintenance, Procedure for soot cleaning, After all repairs or maintenance – Fulton Classic ICX or FB-F Vertical Tubeless Boilers (Hot Water), Gas_Oil Fired User Manual
Page 39: Troubleshooting

Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 4
ICW-IOM-2014-0410
MAINTENANCE
4-9
Procedure for Soot Cleaning
Perform the following:
1. Determine if fl ues are dirty by checking stack temperature with a stack
thermometer. If temperatures are in excess of 600 F (315 C) while the boiler
is operating, the fl ues are likely dirty/restricted in some other manner.
NOTE:
Usually soot cleaning is performed annually, unless the burner setting has
been altered and excessive soot has been produced as a result.
2. Remove burner and fl ue cover plates.
3. Using a wire brush, carefully remove soot from fl ue passages.
4. Clean out plug at lowest part of unit and clean passages between ribs and
bottom of combustion chamber.
5. Remove all soot with a vacuum cleaner. This may be carried out from the
top and via the inspection doors at the bottom.
6. Replace clean-out plug carefully so as not to damage insulation.
7. Replace burner and fl ue cover plates.
After All Repairs or Maintenance
1. Follow “Pre-Start Check List” and all Safety Checks.
2. Fire the boiler and perform combustion safety checks.
3. Analyze combustion throughout the range and verify proper operation of
safety devices.
Troubleshooting
Please refer to Troubleshooting tables that follow.
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.