Installation – Fulton Classic ICX or FB-F Vertical Tubeless Boilers (Hot Water), Gas_Oil Fired User Manual

Page 21

background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

ICW-IOM-2014-0410

INSTALLATION

2-15

Roof

Minimum

6' Above

Any Structure

Within 30'

Support As

Necessary

Install
Appropriate
Weather
Cap

Horizontal
Run 2'

Draft Regulator
(If Necessary)

Draft Regulator
(If Necessary)

Expansion Joints
As Required

Horizontal
Run 2'

Cleanout

Door

60°

(45° Min.)

Cleanout

Door

Cleanout

Door

This Distance
Must Not
Exceed 25%
Of Total Rise

Baffle

3'

3'

30°

Max

Stagger

Entrances

A

A

A-A

Total

Rise

FIGURE 3 - TYPICAL STACK ARRANGEMENT