Installation, Electrical supply, Water supply – Fulton Classic ICX or FB-F Vertical Tubeless Boilers (Hot Water), Gas_Oil Fired User Manual
Page 14: Install water piping

© The Fulton Companies 2014
INSTALLATION
ICW-IOM-2014-0410
SECTION 2
2-8
pump cut sheet.
3. Ensure fuel oil piping is in accordance with local/national requirements.
4. Meet the maximum pressure allowed at the fuel oil pump inlet per the
National Fire Protection Association (NFPA).
5. Oil burners are of a two-pass design system, requiring a return line and a
supply line. The oil pump is factory set per Test Fire Shee
t.
Do not alter the
setting without consulting the factory.
6. A stop valve, a check valve, and an oil fi lter must be installed on the oil
supply line.
7. Ensure there are no loose fi ttings. Loose fi ttings in the fuel oil line will
permit air to enter the fuel line and cause improper fi ring.
Electrical Supply
Adhere to the following for electrical supply installation:
1. Locate electrical schematic diagram, a copy of which is inside of the panel
box.
2. Ensure the information on the electrical drawing corresponds to your
voltage and frequency. Check the supply voltage and make sure that there
is no over- or under-voltage exceeding 10% of the nominal value.
3. Install a separate fuse switch for the contactor and a separate fuse switch
for the circulating pump. If pump motor is 3/4 HP or larger, install an
across-the-line starting switch ahead of the circulating pump motor.
4. Install wiring and ground in equipment in accordance with authority
having jurisdiction or in absence of such requirements the National
Electrical Code, ANSI/NFPA.
5. Provide a fused disconnect sized for the unit. Size fuses according to motor
name plates and local electrical codes.
6. Connect power to the terminal strip as supplied on the inside of the panel
box.
Water Supply
Install Water Piping
All water supplies contain some solids, dissolved gases or dissolved minerals.
These may cause corrosion, deposition and/or fouling of equipment. To prevent
these contaminants from impacting boiler performance, valve operation and
general pipe longevity, each location must be analyzed and treated accordingly.
Adhere to the following for water piping installation:
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
4
CAUTION
Loose fi ttings in the fuel oil line will permit
air to enter the fuel line and cause improper
fi ring.