SECTION 2

ICW-IOM-2014-0410

INSTALLATION

2-5

TABLE 2 - SPECIFICATIONS (REFER TO FIGURE 1)

Model ICW

6

10

15

20

30

Boiler ConnecƟ ons

K. Safety Valve Outlet
IN
MM

0.75
19

0.75
19

1.5
38

1.5
38

1.5
38

L. Safety Valve Inlet
IN
MM

0.75
19

0.75
19

0.75
19

1
25

1
25

M. Water Inlet Size
IN
MM

1.5
38

2
51

2.5
64

2.5
64

3
76

N. Hot Water Outlet Size
IN
MM

1.5
38

2
51

2.5
65

2.5
65

3
76

O. Boiler Drain Size
IN
MM

1
25

1
25

1
25

1.25
32

1.25
32

Approx. Shipping Weights
LB
KG

1700
771

2000
910

2380
1080

3400
1542

4780
2168

RaƟ ngs* (sea level to 3000 Ō ) Output
1000 BTU/HR
1000 KCAL/HR

201
51

335
84

502
127

678
171

1017
256

Approximate Fuel ConsumpƟ on at Rated Capacity+

Light Oil
GPH
LPH

1.8
6.8

3
11.4

4.5
17

6
22.7

9
34

Propane Gas
FT3/HR
M3/HR

100
2.8

168
4.8

251
7.1

335
9.5

502
14.2

Natural Gas
FT3/HR
M3/HR

251
7.1

419
11.9

629
17.8

838
23.7

1256
35.4

Natural Gas Boiler ConnecƟ on Size (Std CSD-1)
IN
MM

1
25

1
25

1
25

1.25
32

1.5
38

Oil Inlet ConnecƟ on Size
IN
MM

.25
6

.25
6

.25
6

.25
6

.25
6

Burner Motor HP
3450 RPM/60 CY
2850 RPN/50 CY

1/3

1/3

1/3

1/3 gas
3/4 oil

3/4

Electric Power Requirements - Burner Only (in amps)

120V 60 CY 1 Phase

7.2

7.2

7.2

7.2 gas
13.8 oil

13.8

230V 50/60 CY 1 Phase

3.6

3.6

3.6

3.6 gas
6.9 oil

6.9

208V 50/60 CY 3 Phase

1.9

1.9

1.9

1.9 gas
3.5 oil

3.5

230V 50/60 CY 3 Phase

1.6

1.6

1.6

1.6 gas
3.2 oil

3.2

460V 50/60 CY 3 Phase

.8

.8

.8

.8 gas
1.6 oil

1.6

Water Content
U.S. GAL
LITERS

21
80

35
132

54
204

104
394

208
787

+ ConsumpƟ on based on light oil 140,000 BTU/GAL, Natural Gas 1010 BTU/Ō 3, Propane 2530 BTU/Ō 3.
** CSA gas train size is 2 inches (50.8 mm) Natural gas pressure required/main inlet is 7-11” W.C. LP Gas Pressure required main inlet is 14” W.C. Natural Gas Pressure required/last elbow is
3/5” W.C. and back pressure. LP Gas pressure required/last elbow is 11” W.C. No. 2 Oil Pressure required/oil pump is 230 PSI.
Notes: Model sizes have threaded inlet and outlet as shown on schemaƟ c. For custom fuel trains, consult Factory for sizing and connecƟ ons.