beautypg.com

Warning – Detroit Radiant Products Company LD3 Series User Manual

Page 9

background image

Model Number

Mounting

Angle*

Sides

Front

Behind

Top

Below

40,000 BTU/h MODELS

LD3 (15, 20) - 40 [N, P]

15

15

6

45

45°

58

8

10

45

with 1 side shield

42

8

6

45

with 2 side shields

20

20

6

45

50,000 BTU/h MODELS

LD3 (15, 20, 30) - 50 [N, P]

11

11

6

48

45°

39

8

10

48

with 1 side shield

29

8

6

48

with 2 side shields

16

16

6

48

20 ft. from burner

7

7

6

30

Chart 2.1 •

Clearance to Combustibles in Inches (see Figure 2.1 for Mounting Angles)

* Heaters mounted on an angle between 0° to 45° must maintain clearances posted for 0° or 45°; whichever is
greater.

NOTE: Use high BTU output when determining clearances. The minimum end clearance is 12 in.

Figure 2.1

Mounting Angles

0° Mounting Angle

45° Mounting Angle

0° Mounting Angle

with 1 Side Shield

(P/N: SSE)

0° Mounting Angle

with 2 Side Shields

(P/N: SSE)

Side

Side

Below

Top

Front

Behind

Below

Top

Front

Behind

Below

Top

Side

Side

Below

Top

WARNING

!

Failure to comply with the stated clearances to combustibles may result in
personal injury, property damage and/or death.

9

LD3

Series

2.0

Safety • Clearance to Combustibles

of the proposed installation.

In locations used for the storage of combustible materials, signs must be posted to specify the maximum
permissible stacking height to maintain the required clearances from the heater to the combustibles.
Signs must either be posted adjacent to the heater’s thermostat or in a conspicuous location.

The stated clearance to combustibles represents a surface temperature of 90°F (32°C) above room
temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply,
etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that
adjacent materials are protected from degradation.