50

LD3

Series

5.0

Maintenance

Troubleshooting Guide

Yes

Continued on page 52

5.0

Maintenance

Does the heater have 120 VAC
at the main power connection?

Turn on control

device for heat.

Does the draft

inducer motor

turn on?

Is the pressure

switch light on?

Yes

Pressure switch

is stuck. Replace

faulty switch.

Does the

pressure switch

indicator light

turn on?

Yes

Does the igniter

warm up and

glow red?

Yes

Does the valve

indicator light

turn on?

Yes

Does the gas

valve turn on?

Yes

Check for loose wiring or

restrictions in the hose

connection to the pressure

switch. Are they acceptable?

Is the inlet or outlet of the

heater obstructed, or is

the vent exceeding the

recommended lengths?

No

Remove obstruction or

correct vent lengths.

Replace wiring or hose

connections.

No

No

No

Yes

Find source of electrical problem.

Is the igniter

physically

damaged?

No

Yes

Replace igniter.

No

Check voltage at igniter

sequence (usually 5 to

15 seconds after call

for heat). Is it 120V?

No

Is the inlet or

the outlet of the

unit plugged or

obstructed?

No

Disconnect igniter

and measure the

resistance. Is it

between 50-400

Ω?

Yes

Yes

Replace circuit board.

No

Yes

Yes

Remove

obstruction.

No

Does the gas valve turn on?

Do you see the burner in

the sight glass?

No

Yes

Gas valve indicator

light is burned out.

Replace light.

Check inlet pressure to

the heater. Is it within the

minimum and maximum

allowable range as per the

rating plate?

No

No

Yes

Are the wires to and from the

gas valve properly connected?

No

Adjust inlet pressure.

Yes

No

Correct wiring.

Key

Start
Question

Process
Question

Corrective
Action

No

Yes