Caution, Installation of the gas line to the heater 1 – Detroit Radiant Products Company LD3 Series User Manual

Page 36

background image

36

LD3

Series

3.0

Installation

Gas Supply

Ball Valve w/ 1/8” NPT Inlet Tap

NEUTRAL

EARTH

HOT

- 120V HEATER INPUT -

120V

G W1 W2 R

12”

CAUTION

!

When using a stainless steel flexible gas connector,

do not attach the connector nuts directly to the gas

pipe supply. Connector nuts must be installed to an approved adapter.

Figure 3.24

Gas Connection (Flexible Gas

Connection shown)

Side View

Stainless Steel

Gas Connector

5/8” O.D. Flare to

1/2” NPT Adapter

Figure 3.25

Gas Connection (Flexible Gas

Connection shown)

End View

2 in. max displacement

3 inch minimum

Drip Leg/

Sediment Trap

Heater Movement

Burner Control

Box Side View

Ball Valve w/

1/8” NPT Inlet Tap

Connect the main gas supply line with an approved flexible connector or, if the authority having jurisdiction
requires rigid piping, the use of approved swing joints may be used. If swing joints are utilized, the heater
must be allowed to freely expand and contract without causing undue stress on the gas pipe.

The heater shall not be connected to the building piping system with rigid pipe or semi-rigid metallic tubing,
including copper. When using such material, an intermediate connection device that allows for the heater
expansion must be used.

The gas outlet must be in the same room as the appliance is installed, and must be accessible. It may not
be concealed within or run through any wall, floor or partition. When installing the heater in a corrosive
environment (or near corrosive substances), use a gas connector suitable for the environment. Do not use
the gas piping to electrically ground the heater.

Installation of the Gas Line to the Heater

1

Install a sediment trap / drip leg in the supply line at the lowest spot prior to the gas ball valve. The trap

length shall be at least three inches long. Ideally, the trap would be installed as close as possible to
the shut off.

2

Install manual shut off ball valve with optional 1/8” NPT Test connection towards the supply line. The

manual shut off ball valve must be located within 6 feet of the appliance’s service access door.

3

Install the 5/8 inch flare to ½” NPT adapter piece downstream of the gas valve as shown in Figure

3.24. This piece is typically included with the flexible gas connector, loosely installed on one of the
flare nuts.

NOTE: Keep flare surfaces clean and free of sealing compounds. Only the pipe threads

require sealing compounds.

4

Form the stainless steel flexible connector into a smooth C-shape, allowing approximately 12 inches

between the flexible connector’s end nuts (see Figure 3.24). The connector must reach from the gas
supply to the appliance without stretching, kinking, or twisting.

5

Attach the flexible connector to the 5/8” flare adapter on the gas line and the other end to the 5/8”

flare on the heaters inlet pipe.

DO NOT connect the connector flare nuts directly to pipe threads. Use

only the adapters provided.

DO NOT kink, twist or over-torque the connector when installing.

45°

45°

Burner Control Box End View

5/8” O.D. Flare to

1/2” NPT Adapter