beautypg.com

Notice – Detroit Radiant Products Company LD3 Series User Manual

Page 52

background image

52

LD3

Series

Does the burner

light?

Is the gas supply valve

to the heater in the ‘ON’

position?

Were the gas lines purged

of air?

Continued from page 50

5.0

Maintenance

Troubleshooting Guide

Yes

No

Yes

Does the burner

stay on?

Yes

Does the heater

stay on until

the call for heat

ends?

Yes

Do the burners light and

then shut off immediately

(within 1-2 seconds)?

No

Does the burner stay on

for approximately 8-10

seconds and then shut off?

No

Yes

Turn on gas

supply line.

No

Purge gas

line.

No

Check inlet pressure and

limit switches.

Check circuit board for flash

codes. Consult factory.

No

The heater can shut down due to:
• Improper grounding
• High winds.
• Taking combustion air from the attic.
• Dirty environment.
• Fluctuating gas pressure.
• Pressure switch opening.

Yes

Troubleshooting ends.

For more information, contact

your local representative or the

factory for further assistance.

Yes

No

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed during normal
operation or the heater’s built-in safety mechanisms will be compromised.

NOTICE