beautypg.com

Valves – Liquid Controls LCR-II Installation E3655-E3656 User Manual

Page 22

background image

22

valves

valves WITh 110vaC solenoIds

In order for the LectroCount LCR-II to control valves with

solenoids on 110 VAC circuits, you must install a relay

switch on the positive leg of the solenoid’s circuit.

relay switch specifications:

Switch: SPST (single pole, single throw)
Switch Position: Normally open
Contact Rating: Greater than maximum current

of solenoid

Voltage: +12 VDC

Materials needed for wiring valves with 110 vaC

solenoids:

not supplied with the valve

• SPST relay switch (1 per solenoid)

20 AWG stranded wire (2 per solenoid)

Weatherproof flexible conduit, ½" diameter and ½" NPT

conduit connectors or cable glands

PTFE tape or pipe sealant

84040 Board

To wire 110 vaC solenoids to the lCr-II:

1. Turn off all 100 VAC circuits before beginning the

installation.

2. Install the specified relay switch(es) onto one leg of the

110 solenoid power supply circuit.

3. Connect the relay switch on the S1 power supply circuit

to terminals 15 and 16 on block j13.

4. Connect the relay switch on the S2 power supply circuit

to terminals 17 and 18 on block j13.

Turn off all 110VAC circuits before beginning

the installation.

Disconnect Power (110VAC)