Valves, Valve installation, Disconnect power – Liquid Controls LCR-II Installation E3655-E3656 User Manual

Page 21: Solenoid operated valve cables, Earth grounds for solenoid valves

background image

21

valves

Solenoid 1 Wiring for

Single Stage Valves

Earth/Green (16)

Out7/Black (15)

+12V/Black (14)

84040 Board

SOLENOIDS J13

Jumper from

Terminal 15

to Terminal 18

S1&2

Solenoid 1 and Solenoid 2 Wiring for A2859-11

and 3-Way Two Stage, 2848-11 Two Stage,

E7 Two Stage Wiring

Connector

Block S2

Connector

Block S1

84040 Board

SOLENOIDS J13

Earth/Green (16)

Earth/Green (16)

Earth/Green (19)

Earth/Green (19)

Out7/Black (15)

Out7/Black (15)

Out6/Black (18)

Out6/Black (18)

+12V/Black (14)

+12V/Black (14)

+12V/Black (17)

+12V/Black (17)

2

1

2

1

valve Installation

If installing the valve yourself, please refer to the valve’s

installation and operation manual for mechanical

installation. Instructions for wiring Liquid Controls valves

to the LCR-II are on the following two pages.

Materials needed for wiring valves:

not supplied

with the valve

20 AWG stranded wire (3 per solenoid). Not necessary for

3-Way solenoid valves. Only 2 needed for E7 solenoids.

Weatherproof flexible conduit, ½" diameter and ½" NPT

conduit connectors or cable glands

PTFE tape or pipe sealant

To wire valves to the lCr-II:

1. Attach cable glands and/or conduit connectors to the

solenoid valve(s) and the LCR-II port(s).

2. Thread the wires through piece of weatherproof conduit

that is cut-to-length from the solenoid to a LCR-II port.

3. Run the weatherproof conduit between the solenoid-

operated valve(s) and the LCR-II housing, pull the wires

through the ports, and tighten the connectors.

4. Connect the S1 solenoid-operated valve wires to

terminals 14 and 15 on the j13 terminal block of the LCR-

II CPU board.

5. Connect the S2 solenoid-operated valve wires to

terminals 17 and 18 on the j13 terminal block of the LCR-

II CPU board.

To wire a single stage valves for presetting:

1. Wire the S1 solenoid as instructed above.
2. Run a jumper wire from Terminal 15 to Terminal 18.

Disconnect the power before working on the CPU board.

Disconnect Power

Solenoid operated valve 81527 (3-way LPG solenoid)

has 3 cables potted into the housing. All other

solenoid operated valves on Liquid Controls valves

use cable assembly 81859, which has 2 cables.

Solenoid Operated Valve Cables

The Earth grounds for Terminals 16 & 19 are optional.

The solenoid operated valves are grounded through

the component they are mounted on.

Earth Grounds for Solenoid Valves