-34-

18.

DUAL ALARM OUTPUTS

18.1

OPERATING MODE MENU SELECTION

When setting up the meter, it may be necessary to enable some of the menu items. See Section
9 for further information.

DIGIT SELECT KEY

VALUE SELECT KEY

MENU KEY

Press the

key until ALSEt

(Alarm setup) is displayed.
See Section 9, ALSEt for de-
tailed selection information
for Digits 1 through 5.

1 2 3 4 5

Press to select value for
flashing digit
Digit 1:Relay state in alarm
Digit 2: Latching or non-latch-
ing output
Digit 3: Alarm high, low, or
disabled
Digit 4: Hysteresis or deviation
Digit 5: Time delay

Press

to display status.

Press

again to select

digit. Selected digit will flash.

Press the

key and dEU1b

(Alarm 1 band deviation) or
dEU1H (Alarm 1 hysteresis)
is displayed if ALSEt digit 4 is
not set to 4.

Press

to display value.

Press again to select
digit. Selected digit will flash.

Using to select digit and
to set digit value, enter
deviation value for setpoint 1
Relays turn on and off at
setpoint if value is zero.

Press the

key and dEU2b

(Alarm 2 band deviation) or
dEU2H (Alarm 2 hysteresis)
is displayed if ALSEt digit 4 is
not set to 4.

Press

to display value.

Press

again to select

digit. Selected digit will flash.

Using to select digit and
to set digit value, enter
deviation value for setpoint 2
Relays turn on and off at
setpoint if value is zero.

18.2

NORMAL OPERATION

When deviation and hysteresis are not enabled or deviation is set to zero, the alarm energizes
at and above the setpoint and deenergizes below the setpoint if high alarm is selected. The
alarm energizes at and below the setpoint and deenergizes above the setpoint if low alarm is
selected. The setpoint value is not displayed if the alarm is disabled.