CONTROL BOARD SETUP

HEATER

CLS ON

LOCK MOD

ON

Viking Heater

The operator has an integrated heater that is thermostatically controlled. Activate this
feature when the operator is used in application temperatures down to -20°F (-29°C).

To set the heater to turn on at the Close Limit:

1. Use the “Diagnose” button to scroll through the LCD

menu to “HEATER CLS”

2. Press and hold the “Stop” button on the control board.

3. Press and release the “Diagnose” button to turn this

feature ON and OFF.

Viking Lock Mode

Turning this feature ON will secure the gate at the closed position, preventing
unauthorized manual entry.

NOTE:

If the application requires the gate to be held open for any reason, set the HEATER

ON for both limit positions.

!

IMPORTANT:

A POSITIVE STOP

must be used on the gate at the limit position(s) the

HEATER has been set for.

HEATER

OPN ON

To set the heater to turn on at the Open Limit:

1. Use the “Diagnose” button to scroll through the LCD

menu to “HEATER OPN”

2. Perform steps 2-3 as described above.

Use the LCD Display to activate this feature.

1. Use the “Diagnose” button to scroll throught the LCD

menu to “LOCK MOD”

2. Press and hold the “Stop” button on the control board.

3. Press and release the “Diagnose” button to turn this

feature ON and OFF.