TROubleSHOOTInG

To trouble shoot the gate operator it is important to understand how the LED’s function work.
Note: The power LED functions all the time that power get to the DGC 2000 Controller box . The LED’s

function for thirty minutes from power-up and go off automatically to save power . To verify that the

LED’s are enabled, activate a limit switch momentarily . If the corresponding LED does not light,

press the LED enable switch, located below the LED’s to enable them for another thirty minutes .

Troubleshooting Assumes the following: (which are not necessarily true):

There is 115v AC power to L-1 and neutral at the high voltage terminal .

The LED’s have been enabled (press the LED enable switch if necessary)

All external controls are connected .

There are no loose or “bad” connections .

If an LED is indicating a possible cause to the malfunction, that problem is dealt with first.

THe lefT leD’S

OPEN, CLOSE, STOP, PULSE O/C, SAFETY indicate what external inputs are being activated. If the gate is

stuck open or closed, first verify that one of those LED’s is not on, indicating that an accessory is holding it in

that position.
Note:

The STOP LED will continuously flash three times and pause after the motor has run longer the set-

ting on the motor run timer . The operator will not function again until power has been removed and

re-applied . It is important to determine the cause of this and correct the problem before putting the

unit back into operation .

THe RIGHT leD’S

OPEN LIMIT, CLOSE LIMIT, CLOSE TIMER, OPEN MODE, and CLOSE Mode indicate what operator

functions are taking place. The OVER CURRENT LED lights when the current sensor activates and stays on

until another input of action takes place. This LED can also light if no current is sensed for 15 seconds while the

motor is “being told” to run. Also if, for example, the OPEN LIMIT LED is lit while the open limit switch is not

activated, check for a defective switch. Flashing OVER CURRENT LED indicated low voltage situation.

GaTe wIll nOT Open

OR OpeRaTe

No LED’s are on
Cause

Solution

No power between L1 and

Neutral with power switch on

Check connection from power supply

Check wiring from high voltage terminal to power plug. Replace as necessary
If problem can’t be corrected, you may need to replace the controller

No power between L-1 and

Neutral with power switch off

Check connection from high voltage plug to controller

Check wiring from high voltage terminal to power plug. Replace as necessary.