Page 14: Close timer, Reverse delay, On off

14
ClOSe Delay
If the close time is switched into the circuit, this set of switches adjusts
the length of time the gate stays open before closing automatically. For example,
if you want 45 second you would turn on 32+8+4+1=45 as illustrated below in figure 12.
32
ON
OFF
16 8 4 2 1
Figure 12
MOTOR Run TIMeR
This timer should be set at least 10 seconds or longer than the normal operating time, and
will stop the gate if for some reason the motor runs longer than the switch setting. If this
happens the stop LED will flash 3 times then pause, 3 times then pause, it will continue to
flash until power has been turned off.
SenSITIvITy aDjuSTMenT
This is used to adjust the current level at which the gate will respond to an
obstruction. Turn clock-wise for more sensitive and counter clock-wise for less
sensitive.
Caution:
The current sense feature is designed only to protect the operator and
reduce vehicle damage. It is not intended for pedestrian traffic!
Note:
The setting must always be sensitive enough to respond to an
obstruction, but not so sensitive that it responds without obstruction.
waRnInG alaRM
One to three seconds prior to gate movement.