FLUID COMPONENTS INTERNATIONAL LLC

FLT93 Flow Switch Series

This page is subject to proprietary rights statement on last page

4

Doc. No. 06EN003312 Rev. D

Jumper Placement

Input Power

Relay Energization

Selectable Heater Wattage Control

Jumper Locations (Underlined Jumpers are default)

Relay Contact Configuration

Standard Default Jumper Configuration

J22 SINGLE SPDT (DISABLES ALARM NO. 2)
J23 DUAL DPDT (ONE RELAY PER A LARM)

100-130 V A C 200-260 V A C 21-30 V DC 18-26 V A C

J1

IN

OUT

OUT

OUT

J2

OUT

IN

OUT

OUT

J3

IN

OUT

OUT

OUT

J4

OUT

OUT

OUT

IN

J5

IN

IN

OUT

OUT

J6

OUT

IN

IN

IN

J7

OUT

OUT

IN

OUT

J8

OUT

OUT

IN

OUT

J9

OUT

OUT

OUT

IN

POWER SELECT

JUM PER

FLOW / LEVEL

TEMP

ALARM NO. 1

J20

J21

ALARM NO.2

J18

J19

JUM PER

J32

J12

J13*

J14*

J33

FLT93-F ELEMENT
WA TTAGE (560 OHM HTR)

FLT93-S ELEMENT
WA TTAGE (110 OHM HTR)

0.57

WATTS

0.52

WATTS

3

WATTS

1.75

WATTS

*J13 IS STANDARD FOR FLT-S AND J14 IS STA NDA RD FOR FLT93-F.

0.75

WATTS

0.21

WA TTS

OFF

OFF

0.49

WATTS

0.25

WA TTS

JUM PER

ALARM NO. 1

RELAY DE-ENERGIZED WITH LOW FLOW,
LOW LEVEL (DRY) OR HIGH TEMPERATURE.
RELAY DE-ENERGIZED WITH HIGH FLOW,
HIGH LEVEL (WET) OR LOW TEMPERATURE.

ALARM NO. 2

RELAY DE-ENERGIZED WITH LOW FLOW,
LOW LEVEL (DRY) OR HIGH TEMPERATURE.
RELAY DE-ENERGIZED WITH HIGH FLOW,
HIGH LEVEL (WET) OR LOW TEMPERATURE.

J27

J26

J25

J24

INPUT POWER

FLT93-S 0.75 WATTS FOR AIR OR LIQUID APPLICATIONS (J13)

FLT93-F 0.25 WATTS FOR AIR OR LIQUID APPLICATIONS (J14)

NUMBER OF ALARMS

230 VAC (J2, J5 AND J6), OR FM APPROVAL 120 VAC (J1, J3, J5)

SET TO MONITOR FLOW OR LEVEL SIGNALS (J20).
RELAY ENERGIZED BELOW TEMPERATURE (J25)
SET POINT AT APPROXIMATELY:
250°F (121°C) FOR STANDARD TEMPERATURE,
500°F (260°C) FOR MEDIUM TEMPERATURE,
850°F (454°C) FOR HIGH TEMPERATURE (FLT93-S ONLY).

HEATER POWER

ALARM NO. 1 RED LED
SET POINT POT R26

ALARM NO. 2 GREEN LED
SET POINT POT R25

SET TO MONITOR FLOW OR LEVEL SIGNALS (J20).
RELAY ENERGIZED AT FLOW OR WET (J27)

TWO (J23). EACH ALARM HAS ONE SET OF SPDT CONTACTS.

Alarm Application