10
Technical data
Type 8045
6.5.
electrical data
Power supply
• 18-36 V DC, filtered and
regulated
• oscillation rate: ±5 %
Current consumption
300 mA max. (at 18 V DC)
transistor output do1
• type
• function
• frequency
• Electrical data
• duty cycle if f > 2 Hz
• min. pulse duration if
f < 2 Hz
• protections
• NPN / PNP (wiring dependent),
open collector
• pulse output (by default), user
configurable
• 0-250 Hz
• 5-36 V DC, 100 mA max.
• 1/2
• 250 ms
• galvanically isolated, and
protected against over-
voltages, polarity reversals and
short-circuits
relay outputs (do2 and
do3)
• operating
• electrical data of the load
• max. breaking capacity
• life span
• hysteresis (by default), configu-
rable, normally open
• 250 V AC / 3 A or 30 V DC /
3 A (resistive load)
• 750 VA (resistive load)
• min. 100000 cycles
current output Ao1
• specification
• max. loop impedance
• 4-20 mA, sink or source (wiring
dependent), 22 mA to indicate
a fault
• 1300 W at 36 V DC, 1000 W at
30 V DC, 700 W at 24 V DC,
450 W at 18 V DC
digital input (di1)
• supply voltage
• input impedance
• min. pulse duration
• protections
• 18-36 V DC
• 15 kW
• 200 ms
• galvanically isolated, and pro-
tected against polarity reversals
and voltage spikes
English