beautypg.com

Burkert Type 8045 User Manual

Page 10

background image

10

Technical data

Type 8045

6.5.

electrical data

Power supply

• 18-36 V DC, filtered and

regulated

• oscillation rate: ±5 %

Current consumption

300 mA max. (at 18 V DC)

transistor output do1

• type

• function

• frequency
• Electrical data
• duty cycle if f > 2 Hz
• min. pulse duration if

f < 2 Hz

• protections

• NPN / PNP (wiring dependent),

open collector

• pulse output (by default), user

configurable

• 0-250 Hz
• 5-36 V DC, 100 mA max.
• 1/2
• 250 ms

• galvanically isolated, and

protected against over-
voltages, polarity reversals and
short-circuits

relay outputs (do2 and
do3)

• operating

• electrical data of the load

• max. breaking capacity
• life span

• hysteresis (by default), configu-

rable, normally open

• 250 V AC / 3 A or 30 V DC /

3 A (resistive load)

• 750 VA (resistive load)
• min. 100000 cycles

current output Ao1
• specification

• max. loop impedance

• 4-20 mA, sink or source (wiring

dependent), 22 mA to indicate

a fault

• 1300 W at 36 V DC, 1000 W at

30 V DC, 700 W at 24 V DC,

450 W at 18 V DC

digital input (di1)
• supply voltage
• input impedance
• min. pulse duration
• protections

• 18-36 V DC
• 15 kW
• 200 ms
• galvanically isolated, and pro-

tected against polarity reversals

and voltage spikes

English