beautypg.com

5 electrical circuit diagrams, English – Burkert Type 3003 User Manual

Page 9

background image

9

Technicaldata

7.5 electrical circuit diagrams

symbol

description

FCO

Limit switch ON

FCF

Limit switch OFF

FC1

Additional limit switch 1

FC2

Additional limit switch 2

4 5

6 7

8 9

1

3

2

TP/PE

N

-

Ph

+

1

3

2

TP/PE

N

-

Ph

+

On

Off

On

Off

FC1

FC2

3-point mode

On-Off-Mode

Feedback

Fig. 2:

Open/Closed version

If voltage is applied simultaneously to terminals 2 and 3, terminal 2 is the leading one and the actuator moves to the OPEN position.

note!

Make certain in 3-point mode that the pulse duration of a controller lasts for at least 1 second. A pause time of at least 500 ms is required
before controller activation is repeated. Observe the duty cycle specified on the type label.
Please note the circuit board must remain power supplied to allow heating resistances working.