beautypg.com

8 normal operation, 9 rotary actuators with integrated emergency, Reset 9.1 technical data 9.2 electric wiring – Burkert Type 3003 User Manual

Page 16: 9rotary actuators with integrated emergency reset, 1 technical data, 2 electric wiring, English, Disconnect the card from the power supply, Display normal operation, Type 3003

background image

16

Rotary actuators with integrated emergency reset

specify end positions

All positions are now saved.

Disconnect the card from the power
supply.

8.8 normal operation

display normal operation

G

Switch on card.

The GREEN LED lights up 3x to indicate that the
start process has been implemented correctly.

G

In normal operation the GREEN LED lights up
when the rotary actuator opens the shut-off valve.

R

The RED LED lights up when the rotary actuator
closes the shut-off valve.

G

R

If neither of the LEDs is lit, the actuator is not
actuated.

G

R

The RED and the GREEN LEDs light up if the
torque is too high and the rotary actuator stops.

Change direction of rotation of the rotary
actuator or switch over the voltage OPEN/
CLOSED to restart the rotary actuator!

9

roTary acTuaTors WiTh
inTeGraTeD emerGency reseT

9.1 Technical data

Voltage

18 V DC

Currant nominal 0.8 A
Max. current

2.4 A

Charging time

max. 14 h

Feedback relay for charge state

24 V DC - 1 A max

Permitted ambient temperature

-10 °C - +40 °C

9.2 electric wiring

65

F+

E-

66

17

18

17

18

battery block

control and power

supply card

F+

Wire colour
red

E-

Wire colour
black

Load state

feedback

Loaded battery: closed
contact

1

2

3

1

2

3

D1

D2

Open

N

Ph

A

A

Ph

Open

KM1

N

A1

A2

N

24 V

AC/

DC

B

B

100V-240V 50/60 hz

(100V-350V dc)

15V-30V 50/60 hz

(12V-48V dc)

On / Off Mode

KM1 - Customer

contactor switch

Suggestet customer

wiring

Actuator

wiring

Total security mode

safety block

Fig. 10: Electric wiring

english

Type 3003