4 type label, 7 technical data, 7technical data – Burkert Type 3003 User Manual
Page 8

8
Technicaldata
Do not remove the type label from the rotary actuator!
It is extremely important for identification during installation
and maintenance.
The warranty is void without the type label.
6.4 Type label
3003 / 225431
~
24 V 50/60 Hz
Fluid Control System
s
IP66 OF N°460050/79
24 V
90° 20 Nm 15W
10/11 S46
Protection class, Serial number
(internal)
Type, Identification number
Operating voltage
Torque, Rating
Operating voltage
Fig. 1:
Location and description of the type label
7
Technical DaTa
7.1 conformity
The electromotive rotary actuator Type 3003 conforms to the EC
Directives according to the Declaration of Conformity.
7.2 standards
The applied standards, which verify conformity with the EC Directives,
can be found on the EC Type Examination Certificate and/or the EC
Declaration of Conformity.
7.3 operating conditions
Ambient temperature:
-10 ... +55 °C
-10 °C ... +40 °C (Emergency reset)
Permissible areas
of application:
0 ... 2000 m altitude
Permissible humidity:
< 81 % to 31 °C (88 °F) with linear
decrease as far as 50 % at 40 °C
(according to EN 61010-1)
Protection class:
IP66 with cable plug
7.4 electrical data
Electrical connections: Cable plug according to EN 175301-803
Cable gland ISO M20
Limit switches:
4 adjustable (2 for the motor and 2 addi-
tional ones for feedback signal) -
max. 250 V AC / 5 A
Range of movement:
90° ± 5° (optional 180°, 270°)
Duty rating:
50 % at max. torque
english
Type 3003