beautypg.com

English – Burkert Type 8623 User Manual

Page 30

background image

28 - 8623-2 Standard

english

KFAC Setting the K factor of the second setpoint

The display shows values in the range 0 to 6552. If it is attempted to set a
higher value, the display will jump automatically to 0 and a value must be
entered within the range. The unit corresponds to the value set in the
menu item UNIT.
(factory setting: 46.60).

RFAC Setting the ratio

Settings are possible between 0.00 and 10.0. If it is attempted to set a
higher value, the display will jump automatically to 0 and a value must be
entered within the range. The decimal point cannot be set at the first (left-
hand) position.
(factory setting: 1.00)

Setpoint setting: ratio control

With ratio control, the (controlled) flow rate Q

1

is adjusted such that the specified

ratio to an (uncontrolled) flow rate Q

2

is maintained.

Q

1

= ratio factor * Q

2

Example :

You set the ratio factor 4:

4,00

Flow rate Q

2

:

20 l/h

Flow rate Q

1

is controlled to :

20 * 4 = 80 l/h

increase digit

next digit

2 s

set decimal point

increase digit

next digit

2 s

set decimal point

Fig.: Setting the setpoint: ratio control