24 - 8623-2 Standard
english
The K factor enables the output frequency of the flow rate sensor to be normalized
to the flow rate:
Q
flow rate
k
k factor
f
output frequency of the flow rate sensor
The K factor states the number of pulses per unit volume:
The K factor should be taken from the data sheet of the flow rate sensor used or
the fitting used. The volume base of the K factor determines the unit of flow rate,
e.g:
resulting in a flow rate in litre per time base.
Q
1
k
f
k
Impuls
V
k
46,60
Impulse
Liter
6.6.3
KFAC - setting the K factor
ATTENTION!
The K factor must be set to agree with the unit chosen.
The display shows values in the range 0 to 6552. If it is
attempted to set a higher value, the display will jump
automatically to 0 and a value must be entered within the range
(factory setting: 46.60).
increase digit
next digit
2 s
set decimal
point
Fig.: setting the K factor
- Type 1062 (112 pages)
- Type 1050 (4 pages)
- Type 8750 (64 pages)
- Type 8750 (82 pages)
- Type 8681 (40 pages)
- Type 8681 (90 pages)
- Type 8798 (106 pages)
- Type 8798 (2 pages)
- Type 8791 (4 pages)
- Type 8718 (34 pages)
- Type 8792 (118 pages)
- Type 8791 (15 pages)
- Type 8792 (136 pages)
- Type 8792 (252 pages)
- Type 8791 (28 pages)
- Type 8791 (21 pages)
- Type 8791 (154 pages)
- Type 8791 (106 pages)
- Type 8791 (184 pages)
- Type 0911 (76 pages)
- Type 0911 (46 pages)
- Type 0911 (64 pages)
- Type 0911 (84 pages)
- Type 1058 (31 pages)
- Type 1060 (4 pages)
- Type 1066 (112 pages)
- Type 1067 (158 pages)
- Type 1077-2 (33 pages)
- Type 1094 (12 pages)
- Type 1094 (41 pages)
- Type 1094 (82 pages)
- Type 1094 (126 pages)
- Type 1115 (25 pages)
- Type 1150 (99 pages)
- Type 1541 (2 pages)
- Type 5142 (6 pages)
- Type 8619 (40 pages)
- Type 8619 (134 pages)
- Type 8620 (177 pages)
- Type 8622 (4 pages)
- Type 8623 (90 pages)
- Type 8625 (118 pages)
- Type 8624 (124 pages)
- Type 8718 (254 pages)