Technical data for the overall system – Burkert Type 8644 User Manual
Page 29
8644/Rockwell - 25
S
YSTEM
D
ESCRIPTION
Technical data for the overall system
Voltage supply:
Rated voltage
24 V/DC
Tolerance
- 15% / + 20%
Valve types 0460, 0461
- 10% / + 10%
Valve type 6524 (2x 3/2-way)
- 15% / + 10%
Current carrying capacity:
Logic area
1 A
24 V area
2.5 A
Maximum current consumption:
I_module
proportion of current in the logic area of the basic electronic modules
max. 75 mA
I_valve
valve current before and after power reduction
Temperature:
Storage temperature
- 20 to + 60 °C
NOTE
The admissible ambient temperature is depent on the modules used. During assembly, the
crucial factor is the most critical module.
Valve type 6524, 6525, 6526, 6527
0 to + 55 °C
Valve type 0460, 0461
0 to + 50 °C
After the field bus nodes 1734-APB, 1734-ADN and 1734-PDN, 13 modules can be placed
in each case. After this, 13 further modules may be connected in each case by attaching
power supply units. The total number of modules must not exceed 63.
Full configuration, 11 mm add-on dimension
max. 64 valves
Full configuration, 16.5 mm add-on dimension
max. 32 valves
NOTE
Valve type
Valve current
before power reduction
after power reduction
6524
43 mA
28 mA
6524
(2 x 3/2-way)
43 mA
18 mA
6525
43 mA
28 mA
6526
[1 W/ 2 W]
42/85 mA
33/52 mA
6527
[1 W / 2 W]
42/85 mA
33/52 mA
0460
41 mA
-
0461
41 mA
-