Special features of commissioning

On delivery, all valve islands possess a comparable configuration with regard to module addressing.

The first addressable module after the field bus node has the address 62,
all following modules the address 63.

Reason:

If a passive DeviceNet node (1734-PDN) is used, then automatic addressing can only be performed via the
modules directly. Since it is difficult to remove the modules owing to the pneumatic design, the first module
was assigned a different address (62).

NOTE

If an active DeviceNet node is used, automatic addressing must be performed.