beautypg.com

Burkert Type 8696 User Manual

Page 19

background image

19

Start-up

10.3.2. Functions of the keys

The configuration of the 2 keys on the board varies depending on the
operating status (AUTOMATIC / MANUAL).

Key 2

Key 1

Fig. 12: Keys

MANUAL operating status (DIP switch 4 set to ON):

Key

Function

8)

1

Aerate (manually open / close the actuator)

9)

2

Deaerate (manually open / close the actuator)

9)

Tab. 5: Configuration of the keys for MANUAL operating status

AUTOMATIC operating status (DIP switch 4 set to OFF):

Key

Function

1

Press for 5 s to start the

X.TUNE function

2

-

Tab. 6: Configuration of the keys for AUTOMATIC operating status

8)

No function if the binary input was activated with the “Manual/
Auto change-over” via the communications software.

9)

depending on the operating principle of the actuator.

10.3.3. Function of the DIP switches

DIP
switches

Function

ON

DIP

1 2 3 4

1

ON

Reversal of the effective direction of the set-point
value (set-point value 20 – 4 mA corresponds to
position 0 – 100 %), descending (

DIR.CMD)

OFF

Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position
0 – 100 %), ascending

2

ON

Sealing function active. The valve completely closes
below 2 %

10)

and opens above 98 % of the set-point

value (

CUTOFF)

OFF

No sealing function

3

ON

Correction characteristic for adjustment of the oper-
ating characteristic (linearization of the process char-
acteristic

CHARACT)

10)

OFF

Linear characteristic

4

ON

Operating status MANUAL (MANU)

OFF

Operating status AUTOMATIC (AUTO)

Tab. 7: DIP switches

10)

Can be changed via communications software.

english

Type 8696