36
Basicfunctions
7.3.3.
BUS.COMM -
adjust the selection / parameters of the field bus interface
→
Select the field bus interface for the positioner / process controller.
Factory setting: without bus
BUS.COMM
Bus type - only readable
without bus
without bus
Profibus DP-V1
DeviceNet
Figure 27:
BUS.COMM function
When you select a field bus, the corresponding bus parameters can be adjusted.
7.3.4.
RESET -
reset to factory settings
This function can be used to reset the positioner to the factory settings.
RESET
RESET
Execute
Figure 28:
DIR.CMD function
procedure:
→
Connect
→
Click
Execute
.
The parameters of the serial interface are set to the following default values:
9600 Bd, parity NONE and 1 stop bit.
→
If there is a deviation from the settings in the communication DTM, the parameters of the serial
interface are readjusted (either on the device side or PC side with the HART communication DTM, see
chapter “6.2.2. Creating a project for Bürkert positioners”).
7.3.5.
TUNE FUNCTIONS -
automatic adjustment of the positioner / process controller
to the relevant operating conditions
A description of the
TUNE FUNCTIONS may be found in Section “6.3.3. Running the automatic
adjustment for TUNE FUNCTIONS”.
English
Software Tool - 8x92 / 8x93