Error messages – Burkert Type 8793 User Manual
Page 32
32
Operationandfunction
6.6.
error messages
6.6.1.
error messages while the X.TUNE function is running
Display
Cause of fault
remedial action
ERR 1:
No pilot air
No pilot air connected
Connect pilot air
ERR 2:
Pilot air failed during
X.TUNE
Pilot air failure while the
X.TUNE function was
running
Check pilot air supply
ERR 3:
Control system
deaeration side leaking
Actuator or control system deaeration side
leaking
Not possible, device defective
ERR 4:
Control system aeration
side leaking
Control system aeration side leaking
Not possible, device defective
Table 5:
Error messages for X.TUNE
6.6.2.
error messages while the PQ.LIN function is running
Display
Cause of fault
remedial action
ERR 1:
No pilot air or no
change to process
variable
No compressed air connected
No change to process variable
Connect compressed air
Check process and, if required,
switch on pump or open the shut-
off valve.
ERR 2:
Current node (valve
stroke) was not reached
Current node of the valve stroke was not
reached, as
• Pilot air failed during
P.Q’LIN
•
X.TUNE was not run.
Check pilot air
Run
X.TUNE
Check process sensor
Table 6:
Error messages for PQ.LIN
English
Software Tool - 8x92 / 8x93