6520 - 9

english

Check the electrical
connetctions

Ensure the operating voltage is
as given on the rating plate

Implement the pressure supply
with as large a volume as pos-
sible (even for pilot devices
such as pressure regulators,
service units, shut-off valves,
etc.);
minimum operating pressure
≥≥≥≥≥ 2,5 bar,
minimum flow rate 270 l/min
at P connection of valve

1)

Implement the pressure supply
with as large a volume as pos-
sible (even for pilot devices
such as pressure regulators,
service units, shut -off valves,
etc.);
minimum operating pressure
≥≥≥≥≥ 2,5 bar,
minimum flow rate 270 l/min
at P connection of valve

1)

Use silencers or expansion
vessels with correspondingly-
large dimensions.

Clean soiled silencers.

Pressure load the exhaust
channels with pressure pulse to
blow away the dirt; Install a
new pilot or main valve if this
measure is unsuccessful.

5 FAULTS

Insufficient or no
operating voltage;

Pressure supply insuffi-
cient or not present.

Pressure supply insuffi-
cient or not present;

Insufficient venting of
the exhaust channels
due to a silencer that is
soiled or is too small
(back pressure);

Soiling or foreign bodies
in the pilot or main valve.

Valve does not
switch:

Valves switches
delayed or
blows out from
the bleed ports:

1)

In the case of version with reduced flow rate
(ID no. 141 721 Z; ID no. 141 72 S), the flow rate is reduced to 150 l/min.

Remedy

Possible cause

Fault