Use in potentially explosive areas of dust – Burkert Type 6013 User Manual
Page 11
11
Technical data
6.6.
Use in potentially explosive
areas of dust
The device may be used either in the hazardous area of gas
or dust but not in a hybrid mixture.
6.6.1. Electrical data
Electrical data for ignition protection type Ex ia:
Coil
size
L x W x H
[mm]
Mass
[g]
Encoding
Structure
Temp.
of the
coil
*
5
45 x 32 x 41
160
PD89
Diodes in the
coil
+80 °C
PE28
78 x 32 x 41
220
PD93
Diodes in the
device socket
PE29
6
50 x 40 x 41
210
PD94
Diodes in the
coil
PE30
83 x 40 x 41
270
PD95
Diodes in the
device socket
PE31
* Max. surface temperature of the coil [T]
6.6.2. Safety data
Group:
IIIC
Category:
2 D
Ignition protection type:
Ex ia
Max. surface temperature:
T = 80 °C
The coils of type AC10 - 5 and AC10 - 6 in ignition protection type “i”
may be connected to circuits which have the following maximum values:
Max. permitted input voltage (U
i
):
35 V
Max. permitted input current (I
i
):
0.9 A
Max. permitted input power (P
i
):
690 mW
Inductance (L
i
):
~ 0
Capacity (C
i
):
~ 0
Type AC10-6 is suitable for individual assembly only.
6.6.3. Permitted ambient temperature
Montage
Temper-
ature class
AC10 - 5
AC10 - 6
Individual
assembly
T6
-40 ... +60 °C
-40 ... +60 °C
Block assembly
T6
-40 ... +60 °C
Not possible
english
PTB 01 ATEX 2101