General information
4.
gEnErAl infOrmATiOn
4.1.
contact Addresses
germany
Bürkert	Fluid	Control	Systems	
Sales	Center	
Christian-Bürkert-Str.	13-17	
D-74653	Ingelfingen	
Tel.		+	49	(0)	7940	-	10	91	111	
Fax		+	49	(0)	7940	-	10	91	448	
E-mail:	[email protected]
international 
Contact	 addresses	 can	 be	 found	 on	 the	 final	 pages	 of	 the	 printed	
operating	instructions.
And	also	on	the	Internet	at:	
4.2.
Warranty
The	warranty	is	only	valid	if	the	device	is	used	as	intended	in	accordance	
with	the	specified	application	conditions.
4.3.
information on the internet
The	operating	instructions	and	data	sheets	for	Type	0742	can	be	found	
on	the	Internet	at:	
5.
APPlicATiOn cOndiTiOns Of 
ThE dEvicEs
5.1.
short-circuit protection
To protect against short-circuits, either a fuse (max. 3 x I
b
in accordance
with	IEC	60127-2-1)	must	be	connected	upstream	of	each	magnet	
according	to	the	rated	current	of	the	magnet,	or	a	motor	protection	
switch	with	short-circuit	and	thermal	quick	release	(set	to	rated	current).	
If	rated	currents	of	the	magnet	are	very	low,	the	fuse	with	the	lowest	
current	value	is	adequate	in	accordance	with	the	stated	IEC	standard.	
This	 fuse	 may	 be	 housed	 in	 the	 associated	 supply	 unit	 or	 must	 be	
connected	separately	upstream.	The	rated	voltage	of	the	fuse	must	be	
equal	to	or	greater	than	the	indicated	nominal	voltage	of	the	magnet.	
The	breaking	capacity	of	the	fuse	insert	must	be	equal	to	or	greater	
than	 the	 maximum	 short-circuit	 current	 accepted	 at	 the	 installation	
location	(usually	1500	A).
The	operator	must	guarantee	short-circuit	protection	for	models	A	and	
L	of	the	electromagnet.	The	fuse	is	installed	in	the	terminal	box	of	the	
device	for	model	K	of	the	electromagnet.
For	 a	 more	 detailed	 description	 of	 models	 A,	 L	 and	 K	 see	
chapter	
english
PTB 02 ATEX 2173 X