English, Trouble shooting maintenance – Burkert Type 0450 User Manual
Page 18
![background image](/manuals/329806/18/background.png)
16 - 8640-0450
M
AINTENANCE
AND
T
ROUBLE
S
HOOTING
english
The valves work without maintenance, even when running dry.
Trouble shooting
Maintenance
Fault
Possible cause
Remedy
Valves do not switch
Operating voltage not present or
insufficient
Check the electrical connection
Provide operating voltage acc. to nameplate
Manual override knob not in neutral
position
Turn knob to zero position
Pressure supply insufficient or not present
Execute pressure supply with as large a
volume as possible (also for upstream
devices such as pressure controllers,
maintenance units, shut-off valves, etc)
Minimum operating pressure > 2 bar
Valves switch with
delay or blow out at
the vent connections
Pressure supply insufficient or not present
Execute pressure supply with as large a
volume as possible (also for upstream
devices such as pressure controllers,
maintenance units, shut-off valves, etc)
Minimum operating pressure > 2 bar
Venting of exhaust air channels insufficient
because silencers are too small or
contaminated (backpressure)
Use matching, large-sized silencers or
expansion vessels.
Clean the contaminated silencers.
Contamination or foreign bodies in pilot or
main valve
Pressurized the exhaust air channels in
pulses to blow out contamination
Install a new pilot or main valve if pulses of
compressed air bring no result.
Leaky valve blocks
Flat seals missing or wrongly positioned
between valve and baseplate
Insert missing seals or replace damaged
seals.