Flowline LU29-1 EchoSonic II User Manual
Page 23

23 MAR 11
EchoSonic II
23 of 24
Rev B
MN300610
Factory Defaults Table
Part
Number
Sensor
Height
Fill
Height
Loop
Fail-Safe
Output
at Empty
Startup
Condition
LU27-01
LU27-11
300 cm
(118.1”)
290 cm
(114.1”)
Overfill
(22 mA)
4 mA @
Bottom
Empty
LU23-01
LU23-11
550 cm
(216.5”)
530 cm
(208.7”)
Overfill
(22 mA)
4 mA @
Bottom
Empty
LU28-01
LU28-11
800 cm
(315.0”)
780 cm
(307.1”)
Overfill
(22 mA)
4 mA @
Bottom
Empty
LU29-01
LU29-11
1000 cm
(393.7”)
980 cm
(385.8”)
Overfill
(22 mA)
4 mA @
Bottom
Empty
Testing the Transmitter
1. Connect a multimeter in series with the black wire to read the current output.
2. Verify that the current increases (tank filling) and decreases (tank emptying) appropriately
in the calibrated span.
3. If not, carefully observe and attempt to correlate any installation, level or application event
for more specific troubleshooting direction.