Delta Controls DPT-2000 User Manual
Page 7
5 IOM-DPT-A: FEB 2014
Appendix Exd.01
In danger zone don’t unscrew transmitter covers and don’t change the display position or
its back lighting.
In case of transmitter calibration outside danger zone is possible communicator connecting to
D
= 240Ω),
closed with jumper at
D
resistor can be
use then, when it is necessary to communicate with transmitter from its terminals and the load
resistance (Ro) in current loop is lover then 250Ω. Than
be open.
Permissible gap of joint is smaller than this was defined in norm EN 60079-1:2008 and can not be
greater than passed value on fig. 7.
Blocking cover method before unscrewing and plumbing possibility is shoved at fig 8.
It is not permitted to repair or otherwise interfere with the transmitter’s electrical circuits
in any way. Damage estimation and repair possibility may be assessed by the
manufacturer or another authorized party only.
Table 1 Permitted
packing glands
.
Type of packing glands Producer
Screw
Feature
Other marking
No of certificate
Note
501/423
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A Baseefa 06 ATEX 0056X
501/421
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A Baseefa 06 ATEX 0056X
ICG 623
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A Baseefa 06 ATEX 0058X
501/453
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A Baseefa 06 ATEX 0056X *
501/453/RAC
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A Baseefa 06 ATEX 0056X *
501/453/Universal
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A Baseefa 06 ATEX 0057X *
ICG 653
HAWKE
M20x1,5
Exd IIC
dimension OS, O, A Baseefa 06 ATEX 0058X *
8163/2-A2F
STAHL
M20x1.5
EXd IIC
SIRA06ATEX1188X
A2F, A2FRC, SS2K
CMP-
Products
M20x1,5
Exd IIC
SIRA06ATEX1097X
E1FW, E1FX/Z,
E2FW, E2FX/Z
CMP-
Products
M20x1,5
Exd IIC
SIRA06ATEX1097X
*
T3CDS, T3CDSPB
CMP-
Products
M20x1,5
Exd IIC
SIRA06ATEX1283X
*
PX2K, PXSS2K,
PX2KX, PXB2KX
CMP-
Products
M20x1,5
Exd IIC
SIRA06ATEX1097X
*
Table 2. permitted plugs
Type of plug
Producer
Screw
Feature
Other marking
No of certificate
Note
AGRO AG M20x1,5
Exd IIC
Nr kat.
475
HAWKE
M20x1,5
Exd IIC
477
HAWKE
M20x1,5
Exd IIC
*) for special cable only.
i
i
i